Parameter Viewer

Document ID ca-gcdwqgtd-2014-02-05-14 Title Guidelines for Canadian Drinking Water Quality: Guideline Technical Document – Turbidity URL https://www.canada.ca/en/health-canada/services/publications/healthy-living/guidelines-canadian-drinking-water-quality-turbidity/page-15-guidelines-canadian-drinking-water-quality-turbidity.html Jurisdiction /ca Subdomain(s) Drinking water, Water treatment Language en Status completed Analyzed at 2026-03-17 15:02:48.954752+00:00 Relevance Technical guidance for optimizing filtration to meet turbidity targets.

Q Qualitative Requirements (7)

Req ID Category Intent Legal Status Name Subdomain(s) Context Conditions Confidence
#Q001designtreatmentrecommendedFiltration System Design and Operationdrinking waterFiltration systems should be designed and operated to reduce turbidity levels as low as possible.high
#Q002treatmenttreatmentmandatoryFiltration Technology Optimizationdrinking waterIn order for utilities to achieve a treated water turbidity target of less than 0.1 NTU, the filtration technology needs to be appropriately designed and the process must be optimized.When utilities aim to achieve a treated water turbidity target of less than 0.1 NTUhigh
#Q003operationaloperationalguidancePlant Optimization Programsdrinking waterUtilities may achieve plant optimization by following plant optimization programs and setting plant-specific filter performance goals.high
#Q004operationaloperationalguidanceAlternative Filtration Goal Settingdrinking waterFor filtration technologies such as slow sand and diatomaceous earth, a similar approach to data collection, filter self-assessment and performance goal setting can be used to help achieve a filtered water target of 0.10 NTU or less.Applicable for filtration technologies such as slow sand and diatomaceous earthmedium
#Q005operationaloperationalguidanceFilter Self-Assessment Information Usagedrinking waterThis information can be used in the filter self-assessment process to help identify performance-limiting factors, which can then be modified to facilitate filter optimization.During filter self-assessment for slow sand and diatomaceous earth technologiesmedium
#Q006administrativeoperationalguidanceBasis for Plant-Specific Goalsdrinking waterIn addition, the PSW individual filter performance goals outlined above can be used as the basis for establishing plant-specific goals for slow sand and diatomaceous earth filtration technologies.Establishing goals for slow sand and diatomaceous earth filtration technologieshigh
#Q007operationalhealthrecommendedFiltration Technology Striving Goaldrinking waterAccordingly, filtration systems that use conventional, direct, slow sand or diatomaceous earth technologies should strive to achieve a treated water turbidity target of less than 0.1 NTU at all times.Applicable to conventional, direct, slow sand or diatomaceous earth technologieshigh

P Quantitative Requirements (8)

Req ID Category Intent Legal Status Name Subdomain(s) Limit Type Limit Value Context Conditions Confidence
#P001physicaltreatmentrecommendedTreated water turbiditydrinking watertreatment_goal< 0.1 NTUAt all times for conventional, direct, slow sand or diatomaceous earth technologiesFiltration systems should strive to achieve this targethigh
#P002physicaloperationalguidanceFiltered water turbiditydrinking watertreatment_goal< 0.10 NTU95 percent of the time based on values recorded at 15 minute time intervals (or more frequent)PSW goals for achieving the Excellence in Water Treatment Award levelhigh
#P003physicaloperationalguidanceMaximum filtered water turbidity goaldrinking watertreatment_goal<= 0.30 NTUPSW goals for achieving the Excellence in Water Treatment Award levelhigh
#P004physicaloperationalguidanceTurbidity during backwash recovery perioddrinking watertreatment_goal> 0.10 NTUMaximum backwash recovery period goal of 15 minutes (time turbidity is above 0.10 NTU)During backwash recoveryhigh
#P005physicaloperationalguidanceCombined filter effluent turbiditydrinking watertreatment_goal< 0.10 NTU95 percent of the timePSW goals for achieving the Excellence in Water Treatment Award levelhigh
#P006physicaltreatmentguidanceFiltered water target (slow sand and diatomaceous earth)drinking watertreatment_goal<= 0.10 NTUFor filtration technologies such as slow sand and diatomaceous earthA similar approach to data collection, filter self-assessment and performance goal settinghigh
#P007operationaloperationalguidanceMaximum backwash recovery period goaldrinking watertreatment_goal<= 15 minutesDefined as the duration where turbidity remains above 0.10 NTUPSW goal for Excellence in Water Treatment Award levelhigh
#P008operationaloperationalguidanceFiltered water turbidity monitoring frequencydrinking watertreatment_goal<= 15 minutesMaximum interval for recording filtered water turbidity valuesPSW goal for Excellence in Water Treatment Award levelhigh

D Definitions (4)

Req ID Category Name Context Confidence
#D001PSWPartnership for Safe Waterhigh
#D002AWWAAmerican Water Works Associationhigh
#D003Programme d'excellence en eau potableProgram for excellence in drinking waterhigh
#D004Maximum backwash recovery period goaltime turbidity is above 0.10 NTUhigh